Property Description: |
(2) story single family home with daylight basement |
Property age: |
Built 2005 per listing |
Occupancy Status: |
Occupied |
Inspection Date: |
03/13/2012 |
Inspection Time: |
2:45 P.M. – 6:00 P.M. +- |
Weather Conditions: |
Light rain and snow, 35 deg F +- |
Summary of Inspection....................................................................................................... 3
Electrical System................................................................................................................. 5
Plumbing System................................................................................................................. 7
Water Heater....................................................................................................................... 9
Heating System................................................................................................................. 11
Site..................................................................................................................................... 13
Building Exterior............................................................................................................... 15
Garage............................................................................................................................... 17
Dining Room and Den...................................................................................................... 20
Kitchen and Nook............................................................................................................. 21
Powder Room.................................................................................................................... 23
Family Room..................................................................................................................... 24
Hallways............................................................................................................................ 25
Master Bedroom Suite....................................................................................................... 27
Bedrooms 2 and 3............................................................................................................. 29
Main Bathroom and Utility Room.................................................................................... 30
Bonus Room...................................................................................................................... 31
Basement........................................................................................................................... 33
Attic................................................................................................................................... 34
Structural Pest Inspection Diagram................................................................................... 36
All items listed in the Summary of each section are listed below. Additional comments may be written in the body of the report. Please read the entire report. All items listed below should be further evaluated, inspected, modified, and/or corrected by a licensed professional in that corresponding or related trade.
WDO refers to “Wood Destroying Organism” as defined by the Washington State Department of Agriculture
- Items in this font are general comments throughout report.
- Items in this font are considered a minor cost and/or cosmetic.
- Items in this font are considered a substantial cost or an extreme safety concern.
Electrical System
- Missing panel knockouts should be filled at the generator switching panel
Plumbing System
- Recommend consultation with fire control system installer as to the operation of the system and to identify the unconnected wire adjacent to the system
Water Heater
- TMP relief line is to be within the upper 6” of the tank and drain by gravity to the exterior. This could have been accomplished by extending the line to the rear of the house
- Possible failure of the water heater expansion tank (appears filled with hot water)
Heating System
- Recommend servicing of furnace by a licensed furnace technician and every (2) years thereafter. There is no visible tag that this furnace has ever been serviced
- Minor odor of gas at the furnace. Recommend further verification of no gas leaks by a licensed heating contractor
Site
- Vegetation in contact with structure (WDO conducive condition)
- Steps facing the garage do not comply with code as of the date of construction
- Recommend screen all gaps at the front deck to prevent animal entry
- Air conditioned compressor should be leveled to prevent premature wear
Building Exterior
- Evidence of bird intrusion at the Master bedroom area
- Recommend clean moss and debris from the roof. Do not pressure wash the roof
Garage
- Evidence of structural movement of the rear garage wall. There is a gap of 1” +- between the garage slab and the foundation wall at the rear center area of the garage. A bulge in the wall (siding) is visible at the exterior. The bulge appears greater at an area lower than the level of the garage slab. The adjacent wall of the basement was poured with step downs indicating that backfill was intended behind the garage wall. Standard foundation walls are generally permitted a maximum of 30” of unbalance fill. Unable to verify if this foundation wall was designed as a retaining wall. Recommend further evaluation from a licensed structural engineer.
- All gaps in the drywall should be sealed (ceiling area)
- (2) rear electrical outlets are not GFCI protected
- Heat ducts running through the garage should be properly sealed and insulated
Dining Room and Den
Kitchen and Nook
Powder Room
Family Room
Hallways
Master Bedroom Suite
- Door to bathroom does not latch
- Soaking tub spout is loose from tub deck
Bedrooms 2 and 3
Main Bathroom and Utility Room
Bonus Room
- Sink waste line valve should have a cover
Basement
- Possible moisture seepage at (2) locations. Recommend seal with hydraulic concrete and continue to monitor
- Completion of the basement would require insulation at the exterior walls
- Completion of basement would require additional electrical outlets
- Recommend verification from a licensed heating contractor as to whether the furnace system has adequate capacity to heat the basement. It may be more economical to heat this area by a separate furnace
- Addition of new walls within the basement may affect the design of the fire control system
Attic
|
Main panel # 1 |
|
Main panel # 2 |
|
|
No evidence of over heating |
|
No evidence of over heating |
|
|
|
Service
|
|
Type: |
Underground |
Meter Location: |
Side of garage |
Voltage: |
240 |
|
|
|
|
Panel
|
|
Location: |
Garage |
Manufacturer: |
Siemens |
Type: |
Dual bus bar |
Panel Rating: |
(2) 200 AMP |
Main Disconnect: |
(2) 200 AMP |
Serv. wire Size/ Rating: |
(2) 200 AMP |
Sub-panel: |
Yes, in the basement |
Grounding: |
Copper to exterior ground rod, limited visibility |
Panel Clearance: |
30” wide, 3’ in front as required |
|
- Missing panel knockouts should be filled at the generator switching panel |
|
Exterior grounding |
|
Panel knockouts should be filled |
|
|
Sub panel in the basement |
|
|
|
|
|
Breakers/ Wiring
|
|
Type: |
Copper romex |
Breakers: |
No visible defects |
|
- Arc fault breakers tested |
|
|
Domestic Water
|
|
Supply: |
Public water per listing, not included in this inspection |
Supply Pipe: |
Copper where visible |
House Piping: |
Copper where visible |
Pipe Condition: |
Satisfactory where visible |
Main Water Shut off: |
@ basement |
|
|
Domestic Water Shut off |
|
|
Fire control system |
|
Unconnected wires at fire control system |
|
|
|
|
|
Sanitary Sewer
|
|
Discharge: |
Public sewer per listing, ,not included in this inspection |
House Piping: |
ABS where visible |
Pipe Condition: |
Satisfactory where visible |
|
Septic alarm system |
|
|
|
|
Water Heater
|
|
Location: |
Basement |
Make/ Model: |
Bradford White built 2005 per serial number |
Fuel Type: |
Natural gas |
Capacity: |
75 gallon |
|
|
|
|
Useful Life
|
|
Est. Useful Life new: |
12 years |
Est. age of heater: |
7 years +- |
|
Data plate |
|
|
|
|
|
||||
|
|
|
|
||||
|
Safety
|
|
|
||||
|
TMP valve: |
- TMP relief line is to be within the upper 6” of the tank and drain by gravity to the exterior. This could have been accomplished by extending the line to the rear of the house |
|
||||
|
Earthquake Straps: |
Installed |
|
||||
|
Expansion Tank: |
- Possible failure of the water heater expansion tank (appears filled with hot water) |
|
||||
|
Flame Rollout: |
No visible evidence
|
|
||||
|
TMP valve is substantially above the heater
|
|
Expansion tank appears heated |
|
|||
|
|
|
|
Flue
|
|
Secure: |
Inspected |
Clearances: |
As required where visible |
Draft Hood: |
Inspected |
|
|
|
|
Water Temperature
|
|
Safe water temperature: |
120 deg F per industry standards |
Measured temperature: |
- Not measured |
|
|
|
Furnace
|
|
Location: |
Basement |
Make/ Model: |
Trane XR80 manufactured 8/2003 |
Fuel Type: |
Natural gas |
BTUH Input: |
120,000 |
BTUH Output: |
- Not noted on furnace, Likely 80% of 120,000 = 96,000 BTUH |
Efficiency Rating: |
Mid-efficiency |
|
|
|
|
Useful Life
|
|
Est. Useful Life new: |
25 years |
Est. age of furnace: |
8 years +- |
|
- Recommend servicing of furnace by a licensed furnace technician and every (2) years thereafter. There is no visible tag that this furnace has ever been serviced |
|
|
|
|
Heat Exchanger |
|
Visible Inspection: |
No visible defects, limited visibility |
Gas detection test: |
No gas leak detected |
Burner test: |
No burner irregularities detected |
|
|
|
|
Operation |
|
Thermostat: |
Programmable @ floor 1 hall |
Disconnect: |
Switch on furnace |
Combustion Air: |
Appears adequate |
Filter: |
Located below furnace |
|
Furnace filter location |
|
|
|
|
|
Flue/ Gas Piping |
|
Flue Secure: |
Inspected |
Flue clearances: |
Per requirements where visible |
Gas Piping: |
Drip leg installed |
|
- Minor odor of gas at the furnace. Recommend further verification of no gas leaks by a licensed heating contractor |
|
|
Site
|
|
Grade at structure: |
Adequate grade away |
Earth to wood contact: |
Clearance as required |
Vegetation contact: |
- Vegetation in contact with structure (WDO conducive condition) |
Roof drain discharge: |
Underground discharge |
|
Vegetation in contact with the structure |
|
|
|
|
|
||||
|
|
|
|
||||
|
Driveway
|
|
|
||||
|
Type: |
Asphalt and Concrete |
|
||||
|
Condition: |
Satisfactory |
|
||||
|
Trip Hazard: |
None |
|
||||
|
|
|
|
||||
|
|
|
|
||||
|
Front walks/ steps
|
|
|
||||
|
Type: |
Concrete and wood |
|
||||
|
Condition: |
Satisfactory |
|
||||
|
Trip Hazard: |
- Steps facing the garage do not comply with code as of the date of construction |
|
||||
|
|
- Recommend screen all gaps at the front deck to prevent animal entry |
|
||||
|
|
|
|
||||
|
Animals can enter beneath the deck |
|
Steps have excessive and inconsistent height |
|
|||
|
|
|
|
Rear walks/ steps
|
|
Type: |
Concrete |
Condition: |
Satisfactory |
Trip Hazard: |
None |
|
|
|
|
Miscellaneous
|
|
Overhead Power Lines: |
N/A |
Retaining Walls: |
None that affect structure |
Underground Oil Tank: |
No visible evidence |
Irrigation System: |
- Not noted |
|
- Air conditioned compressor should be leveled to prevent premature wear |
|
Out of level compressor Air conditioning not tested due to exterior temperature |
|
|
|
|
|||||
|
General Condition
|
|
|||||
|
Structural Movement: |
No visible evidence |
|
||||
|
Exterior doors: |
Satisfactory |
|
||||
|
Windows (ext. cladding): |
Satisfactory |
|
||||
|
|
|
|
||||
|
|
|
|
||||
|
Siding
|
|
|
||||
|
Type: |
Wood |
|
||||
|
Condition: |
Satisfactory |
|
||||
|
Window/Door Flashing: |
Satisfactory |
|
||||
|
Caulking: |
Satisfactory |
|
||||
|
|
|
|||||
|
|
|
|
||||
|
Possible missing screen at a vent See image to right |
|
Evidence of bird intrusion |
|
|||
|
|
|
|
Roof
|
|
Estimated Pitch: |
4:12 |
Material: |
Composition |
Layers: |
1+ |
How Inspected: |
From floor 2 and from the front and rear yard |
Condition: |
Satisfactory |
|
- Recommend clean moss and debris from the roof. Do not pressure wash the roof |
Ventilation: |
Eave and ridge vent |
Plumbing Vents: |
Satisfactory |
Flues: |
Satisfactory |
Flashing: |
Satisfactory |
|
Moss buildup on roof (typical) |
|
|
|
|
|
Gutters/ Downspouts
|
|
Type: |
Continuous metal |
Condition: |
Satisfactory, debris in gutters |
|
|
|
|
Electrical
|
|
Outlets: |
Tested, GFCI protected |
Switches/Lights: |
Tested |
|
|
|
|
Plumbing
|
|
Hose Bibs: |
Anti-siphon |
Gas Piping: |
Inspected |
|
|
|
|
Decks
|
|
Structure: |
Pressure treated joists |
Decking: |
Cedar |
Condition: |
Satisfactory |
Connection to Structure: |
Lag bolts |
Trip Hazard: |
None |
Handrails: |
As required |
Barricades: |
As required |
|
Deck connection to the house |
|
Type: Attached |
|
|
General Room Condition
|
|
Visibility: |
Space is occupied |
Structural Movement: |
- Evidence of structural movement of the rear garage wall. There is a gap of 1” +- between the garage slab and the foundation wall at the rear center area of the garage. A bulge in the wall (siding) is visible at the exterior. The bulge appears greater at an area lower than the level of the garage slab. The adjacent wall of the basement was poured with step downs indicating that backfill was intended behind the garage wall. Standard foundation walls are generally permitted a maximum of 30” of unbalance fill. Unable to verify if this foundation wall was designed as a retaining wall. Recommend further evaluation from a licensed structural engineer. |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Slab: |
- Minor cracks in the slab. The slab appears to have a slight upwards bulge at the cracks which also correspond to the bowing foundation wall at the rear of the garage |
Approximate 1” gap between the slab and the garage wall.
The gap would have occurred after the slab was poured
(not when the foundation was backfilled)
Approximate 8’ high unbalance foundation wall at the rear of the garage
|
Band board is the approximate height of the slab
|
|
Step down of the adjacent wall in the basement suggests that a sloping backfill was intended behind the rear garage foundation wall |
|
|
|
|
|
Safety
|
|
Fire separation: |
|
Ignition point > above FF: |
In compliance |
Safety barricade to mech.: |
In compliance |
|
|
|
|
Garage Door
|
|
Type: |
Metal roll-up |
Springs & Fasteners: |
No visible defects |
Auto Reverse: |
Tested |
Photocell reverse: |
Tested |
Remote openers: |
Not present |
|
|
|
|
Electrical
|
|
Switches/Lights: |
Tested |
Outlets: |
All visible tested |
|
|
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Plumbing
|
|
Functional flow: |
Appears adequate |
Hot/ Cold: |
Tested |
Drainage: |
Appears adequate |
Visible leaks: |
None visible |
Caulking: |
Satisfactory |
Toilet Secure: |
Satisfactory |
Fixtures: |
No visible defects |
|
|
|
|
Heating
|
|
|
- Heat ducts running through the garage should be properly sealed and insulated |
|
Heat loss at ducting |
|
Heat loss at ducting |
|
|
|
General Room Condition
|
|
Visibility: |
Rooms are vacant |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
Smoke Detector: |
Yes, in Den |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Location: Floor 1 |
|
|
General Room Condition
|
|
Visibility: |
Rooms are occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
Cabinets: |
Satisfactory |
Countertops: |
Satisfactory |
|
|
|
|
Appliances
|
|
Dishwasher: |
Tested full cycle |
Dishwasher high loop: |
Visible |
Oven: |
Tested |
Cooktop: |
Tested |
Microwave: |
Not tested |
Ventilation: |
Tested |
Refrigerator: |
Tested |
|
|
|
|
Plumbing
|
|
Functional flow: |
Appears adequate |
Hot/ Cold: |
Tested |
Drainage: |
Appears adequate |
Visible leaks: |
None visible |
Disposal: |
Tested |
|
- A garbage disposal is not recommend with a septic system |
Caulking: |
Satisfactory |
Fixtures: |
No visible defects |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested, GFCI protected |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
The nook heat register could be relocated to the island toe-kick to avoid the dropped pipe in the basement |
|
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Location: Floor 1 |
|
|
General Room Condition
|
|
Visibility: |
Room is vacant |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
Mirrors: |
Satisfactory |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested, GFCI protected |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
Mechanical ventilation: |
Tested |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Bath Hardware: |
Satisfactory |
|
|
|
|
Plumbing
|
|
Functional flow: |
Appears adequate |
Hot/ Cold: |
Tested |
Drainage: |
Appears adequate |
Visible leaks: |
None visible |
Caulking: |
Satisfactory |
Toilet Secure: |
Satisfactory |
Fixtures: |
No visible defects |
|
|
General Room Condition
|
|
Visibility: |
Room is occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
|
|
|
|
Fireplace
|
|
Type: |
Sealed gas direct vent |
Tested: |
Ignition tested |
Location: Floors 1, 2, and basement |
|
|
General Room Condition |
|
Visibility: |
Space is occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
Infrared image of entryway (typical) |
|
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
Smoke Detector: |
Yes |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
As required |
Operation: |
Fixed |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory
|
|
|
|
|
Stairwell |
|
Handrails: |
As required |
|
- Handrails from this date of construction were typically required to have continuous handrails. No apparent safety hazard created by the split handrail |
Barricades: |
As required |
Balusters: |
As required |
Trip Hazard: |
None |
|
Split in handrail The stair tread below is not a “landing” |
|
Location: Floor 2 |
|
|
General Room Condition
|
|
Visibility: |
Room is occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
Cabinets: |
Satisfactory |
Countertops: |
Satisfactory |
Mirrors: |
Satisfactory |
|
Furnace flue runs up the boxed in area adjacent to the closet. Noise may occur from the flue as the metal expands and contracts |
|
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested. Bathroom outlets are GFCI protected |
Smoke detector: |
Yes |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
Mechanical ventilation: |
Tested |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
As required |
Operation: |
Tested |
Egress: |
Appears to provide reasonable emergency egress |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
|
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Bath Hardware: |
Satisfactory |
|
|
|
|
Plumbing
|
|
Functional flow: |
Appears adequate |
Hot/ Cold: |
Tested |
Drainage: |
Appears adequate |
Visible leaks: |
None visible |
Caulking: |
Satisfactory |
Toilet Secure: |
Satisfactory |
Tub/Shower surround: |
Satisfactory |
Fixtures: |
Location: Floor 2 |
|
|
General Room Condition
|
|
Visibility: |
Rooms are occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
Smoke Detector: |
Yes |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Egress: |
Appears to provide reasonable emergency egress |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Location: Floor 2 |
|
|
General Room Condition
|
|
Visibility: |
Rooms are occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
- Minor nail pops at the ceiling in the bathroom |
Flooring: |
Satisfactory |
Cabinets: |
Satisfactory |
Countertops: |
Satisfactory |
Mirrors: |
Satisfactory |
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested, GFCI protected |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
Mechanical ventilation: |
Tested |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
Bath Hardware: |
Satisfactory |
|
|
|
|
Plumbing
|
|
Functional flow: |
Appears adequate |
Hot/ Cold: |
Tested |
Drainage: |
Appears adequate |
Visible leaks: |
None visible |
Caulking: |
Satisfactory |
Toilet Secure: |
Satisfactory |
Tub/Shower surround: |
Satisfactory |
Fixtures: |
No visible defects |
Appliances: |
- Not tested as they were full of clothes |
|
|
General Room Condition
|
|
Visibility: |
Room is vacant |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
No visible evidence |
Walls: |
Satisfactory |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
Infrared image of framing (typical) |
|
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
Smoke Detector: |
Yes |
|
|
|
|
Heating
|
|
Source: |
Floor register |
Air Flow/ Heat Gain: |
Satisfactory |
|
|
|
|
Plumbing
|
|
|
|
Sink waste line valve should have a cover |
|
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
Not required |
Operation: |
Tested |
Screen: |
No visible defects |
|
|
|
|
Doors/Millwork
|
|
Operation/latching: |
Tested |
Door condition: |
Satisfactory |
Millwork condition: |
Satisfactory |
|
|
General Room Condition
|
|
Visibility: |
Room is occupied |
Structural Movement: |
No visible evidence |
Moisture Infiltration: |
- Possible moisture seepage at (2) locations. Recommend seal with hydraulic concrete and continue to monitor |
Walls: |
- Completion of the basement would require insulation at the exterior walls |
Ceiling: |
Satisfactory |
Flooring: |
Satisfactory |
|
Possible moisture seepage at (2) locations |
|
|
|
|
|
Electrical
|
|
Switches/Lights: |
All visible tested |
Outlets: |
All visible tested |
|
- Completion of basement would require additional electrical outlets |
Smoke Detector: |
Yes |
|
|
|
|
Heating/ Fire Control
|
|
Source: |
- None |
|
- Recommend verification from a licensed heating contractor as to whether the furnace system has adequate capacity to heat the basement. It may be more economical to heat this area by a separate furnace |
Air Flow/ Heat Gain: |
n/a |
|
- Addition of new walls within the basement may affect the design of the fire control system |
|
|
|
|
Windows
|
|
Glazing: |
No visible defects |
Tempered: |
As required |
Operation: |
Tested |
Screen: |
No visible defects |
Location: Over main body of house |
|
|
|
|||||
|
General
|
|
|||||
|
Visibility: |
Space is vacant |
|
||||
|
Access location: |
Master Bedroom closet |
|
||||
|
How viewed: |
Traversed entire attic space where there is reasonable headroom
|
|
||||
|
Attic (typical) |
|
Attic (low headroom over the bonus room) |
|
|||
|
|
|
|
Moisture
|
|
Roof Ventilation: |
Appears adequate |
Moisture Intrusion: |
No visible evidence |
Bath/Kitchen fans : |
All vent to outside |
|
Ridge vent (typical) |
|
|
|
|
|
Structural
|
|
Structure Type: |
Manufactured trusses |
Sheathing: |
OSB |
Structural Movement: |
No visible evidence |
|
|
|
|
Insulation
|
|
Type: |
Blown in |
Approximate Depth: |
10” +- |
Condition: |
Satisfactory |
|
|
|
|
Flues/Vent Stacks
|
|
Plumbing Stacks: |
All vented to exterior |
Gas Flues: |
No visible defects |
|
Furnace flue |
|
|
|
|
|
Electrical
|
|
Outlets: |
None visible |
Wiring/ junction boxes: |
No visible defects |
|
|
|
|
Structural Pests
|
|
Conducive Material: |
No visible evidence |
Visible Evidence: |
No visible evidence |
|
|
|
|
Nuisance Pests
|
|
Visible Evidence: |
No visible evidence |
Wood Destroying Organisms (WDO) |
|
Conducive Conditions (CC) |
||
WDO-AB |
Anobid Beetles |
|
CC-BG |
Bare Ground |
WDO-CA |
Carpenter Ants |
|
CC-CD |
Conducive Debris |
WDO-DT |
Dampwood Termites |
|
CC-EM |
Excessive Moisture |
WDO-MA |
Moisture Ants |
|
CC-EW |
Earth-Wood Contact |
WDO-OB |
Other Beetles |
|
CC-FC |
Failed Caulking |
WDO-RF |
Rot Fungus |
|
CC-IV |
Inadequate Ventilation |
WDO-ST |
Subterranean Termites |
|
CC-RG |
Restricted Gutter |
|
|
|
CC-VC |
Vegetation Contact |
Inspection Conditions (IC) |
|
|
|
|
IC-CSA |
Crawl Space Access |
|
|
|
IC-IA |
Inadequate Clearance |
|
|
|
No structural pests identified. Conducive conditions include the vegetation in contact with the basement area
|